| UXR100040G |
| Category | Item | Specifications |
| Basic Specifications | Dimensions | 85mm (H) x 360mm (W) x 459mm (D) |
| Weight | ≤20kg |
| Efficiency (full load) | ≥96.3% |
| Standby Power Consumption | Normal standby mode: 13W+/-0.5W; Super standby mode: < 2W@380Vac |
| Cooling Mode | Fan cooling |
| Communication Bus Protocol | CAN Bus |
| No.of Parallel Modules | ≤60 pcs |
| Indicator | Green: normal operation; Yellow: alarm; Red: fault |
| Input Characteristics | Input Voltage | 260Vac~530Vac, 3P + PE |
| Input Current | <80A |
| Grid Frequency | 45Hz~65Hz |
| Power Factor | ≥0.95(8kW≤ output power ≤20kW); ≥0.98(20kW≤ output power ≤40kW) |
| ITHD | ≤5% |
| Output Characteristics | Output Power | 40kW@Output voltage 300Vdc |
| Voltage Range | 50Vdc ~ 1000Vdc, default value: 200Vdc |
| Current Range | 0A~133.3A |
| Ripple Voltage Peak Value Coefficient | ≤1% |
| Electrical Isolation Method | High Frequency Isolation |
| Environmental Conditions | Operating Temperature | -40°C ~ +75°C, output derating at above 55°C |
| Storage Temperature | -40°C~+75°C |
| Relative Humidity | ≤95%RH, non-condensing |
| Altitude | No derating 2000m. When altitude >2000m, operating temperature decreases by 1°C for every 100m. The actual altitude value needs to be set @1000m |
| MTBF | > 500,000 hrs |